ITEM METADATA RECORD
Title: Reducing losses in distribution transformers
Authors: Olivares, JC ×
Liu, YL
Canedo, JM
Escarela-Perez, R
Driesen, Johan
Moreno, P #
Issue Date: Jul-2003
Publisher: Institute of Electrical and Electronics Engineers
Series Title: IEEE Transactions on Power Delivery vol:18 issue:3 pages:821-826
Abstract: This paper examines three methods of reducing distribution transformer losses. The first method analyzes the effects of using aluminum electromagnetic shields in a distribution transformer. The goal of placing electromagnetic shields in the distribution-transformer tank walls is to reduce the stray losses. A 500-kVA shell-type transformer was used in the experiments. The overall results presented indicate that stray losses can be considerably reduced when electromagnetic shielding is applied in the transformer tank. In the experiment, the tank walls were lined with aluminum foil. The possibility of reducing the dielectric losses was shown through experiments in the second method. And the third method of this Work analyzes the behavior of wound-cores losses in distribution transformers, as a function of joint configuration design parameters. The joint configuration used in this paper is called step-lap joint.
URI: 
ISSN: 0885-8977
Publication status: published
KU Leuven publication type: IT
Appears in Collections:ESAT - ELECTA, Electrical Energy Computer Architectures
× corresponding author
# (joint) last author

Files in This Item:

There are no files associated with this item.

Request a copy

 




All items in Lirias are protected by copyright, with all rights reserved.

© Web of science