Title: Comparison of different methods to limit short circuit currents in DC traction networks
Authors: Breugelmans, Sam
Leterme, Willem
Van Hertem, Dirk
Marcelis, Richard
Issue Date: Apr-2014
Host Document: Proc. IET DPSP pages:1-6
Conference: IET DPSP edition:12 location:Copenhagen, Denmark date:31 Mar. - 3 Apr. 2014
Abstract: In this paper, different methods to limit short circuit currents in DC traction networks are compared. Typically, DC traction networks are supplied by the AC grid by means of an uncontrolled diode bridge rectifier. In case of a low-impedance short circuit fault between catenary and rail, the fault current reaches a large value. For densely meshed networks the mechanical circuit breakers can become too slow. The methods studied are applying fault current limiters, faster interruption of fault currents and adding controlled rectifiers. The fault current limiters considered are a reactor and a superconducting fault current limiter (SFCL). For faster interruption of fault currents, a hybrid circuit breaker is investigated. Simulations show that the short circuit current can be limited considerably by installing limitation devices after the rectifiers, when the short circuit occurs close to a substation. Fast interruption of the fault or application of the SFCL results in the strongest reduction of the short circuit current.
Publication status: published
KU Leuven publication type: IC
Appears in Collections:ESAT - ELECTA, Electrical Energy Computer Architectures

Files in This Item:
File Description Status SizeFormat
P058.pdf Published 1164KbAdobe PDFView/Open Request a copy

These files are only available to some KU Leuven Association staff members


All items in Lirias are protected by copyright, with all rights reserved.